ZS5 Haier Air Conditioner (Inverter Split Type), the outdoor compressor is not running, how to troubleshoot?

by vdb35cl5 on 2011-11-12 22:18:31

Article Source: Beijing Haier Air Conditioning Maintenance Center, http://blog.163.com/haierktiao_2012/.

Fault Symptoms: The indoor unit can start and run normally, but the outdoor compressor stops immediately after starting, while the fan operates normally.

Analysis and Inspection: The fact that the compressor can start indicates that the software is basically normal. It is judged that there might be a fault in the protection circuit or sensor circuit. First, the sensor was checked and found to be normal. After disconnecting the power, the resistor R30 (51kΩ/1w) in the circuit was checked, and it was found to be open-circuited, causing the CPU to mistakenly recognize an excessively low voltage and thus trigger the protection shutdown.

Repair Method: After replacing the resistor R30, the fault was eliminated.

Haier Air Conditioner (Inverter Split Type), the outdoor compressor does not operate.